Model 707 Parts
 |
 |
Water quality is a major
problem causing corrosion and mineral build-up. Using a
food service quality water
purifier with scale treatment will keep the 707u
clean. The purified water will eliminate the white
mineral dust that falls from the evaporating air. As
well remove odors and corrosives such as
chlorine and sodium. Common problems with the
707 series are:
- Gap between impeller and motor needs
adjustment.
- Motor corrosion from hard water.
- Not draining the 707 off season causes motor
seizure.
- Impeller and Pump Cap clog.
|
|
Instructions for setting gap: Trion
Impeller Adjustment
These photos show a 707u used in a humidor. The
photo right shows the 707u motor assembly. The
motor still runs fine but the aluminum motor cap
is heavily corroded from chlorine and has a heavy
crust of lime.
The humidor environment runs year round and at
a much higher humidity than a residential home.
When under such heavy usage the water quality is
most important. These photos would be much
different if distilled quality water was used.
The centrifuge effect separates the once
dissolved heavy minerals from the water. The very
fine minerals create a slime. The slime leaves
behind the dried residue in the 707 reservoir pan
shown in photo. |
| |
|
Test your water and consult with local experts on
treatment. Food service quality filters are designed to
keep the equipment clean while producing water free of
bad taste or smell. Pure water is necessary for moist
air with a clean taste and smell. Removing the
chorine smell is important for a humidor.
The filtration process of stripping the water of
minerals can leave water acrid. The acrid water will
cause corrosion. A simple combination
filter will remove the minerals, remove the odors,
and treat the water with a softener that corrects the
high PH. |
|
|
Photo left shows the impeller pump clogged from
the minerals. Removing the pump cap results in
sediment falling out. This sediment caused
un-balance. To clean the impeller, remove the pump
cap. The cap is pressed-in and should simply
pull-out. Run the cap under hot water if
stuck.
The unbalance caused the impeller to became
loose. The setscrew appeared rusted but it was the
brown mineral build-up. The impeller clearance
from the base needs to be set to 1/16". The set
screw was re-secure using a 1/16" allen wrench.
Photo left shows the top of the impeller.
Minerals have been centrifugally separated from
the water. Use a pipe cleaner to clean the 6 small
holes.
At Bel-Aire we use an automotive parts washer
with humidifier cleaning detergent. The re
circulating pump cleans the most difficult
humidifiers or electronic air cleaners.
Water
Treatment &
Filtration | | |
 |
 |
Impeller Pump for 707 Series
|
Retainer Clips Trion 707 Qty 4
|
Vibration Damper Trion 707 Qty 4
|
Center Pan Feet for 707 Qty 4
|
|
|
Extension Nozzle 707 Series
|
|
Motor Base for 707 Series
|
Diffusing Screen for Trion 707
|
Drip Tube Pair 707 Series
|
|
Skuttle Humidifier Filter
|
Mounting Bracket 707 Series
|
Trion 926 Humidity Control
|
Float Assembly 707 Series
|
|
Center Pan for 707 Series
|
|
Motor for 707 Series 240v
|
Centrifugal Atomizer 707U
| |
| |